DSH/DSV/RSH/DBH/RBH Series Dehumidifier. Owner's Manual. Data subject to change without notice. Risk of electric shock. Can cause injury or death. Some installation and service procedures could expose personnel to the risk of electric shock. Electric shock can. Out of airstream. • Indoor installation. • Factory tested at operating conditions. * Models also available without pool water heater. ** Horizontal design also available. Indoor Pool/ Whirlpool. Light Commercial and. Residential Dehumidifiers. DSV Series (Vertical Airflow, Corner Installation). Dectron (a division of Dectron. Dectron, Inc. Owner's Manual DSH/DSV/RSH/DBH/RBH Series Dehumidifier. Data subject to change without notice. Control Signals. The communication system between the controller and a remote display (if any) is based on. ANSI/IEEE RS-485. DS/DSV/RS 010-080 Series Dehumidifier. Owner's Manual. Interface Map. Dectron, Inc. Data sub ect to change without notice. /C option installed latent- sensible heating mode & auxiliary pool water heater airflow sensor option installed outdoor temperature sensor option installed.
Owner’s Manual Owner’s Manual DS/DSV/RS S010-080 Series Dehumidifier Diagnostics - Controller Operation SYMPTOM POSSIBLE CAUSE CHECKS & ACTION Code #9 High limit evaporator. (Over 80°F for 5 minutes) 3. Biomecanica Basica Del Sistema Muscoesqueletico Nordin Pdf To Excel there. Improperly adjusted or defective hotgas bypass valve (units with A/C only) 4. Excessive air flow 5 Excessive load 6. Download Free Software Inkspot Illustration Program. Improper return-air duct connection at unit (e.g., 90° elbow very close to the unit) Uneven air distribution across the evaporator and bypass damper prevents normal air cooling.
• Check to see if line from hot gas bypass valve to distributor is hot. Verify that the three-way valve may be jammed: 1. Force the suspect valve to operate and check for changes in operating temperatures and pressures. If no changes occur, then the valve is completely jammed and must be replaced. If the unit runs fine in pool heating and/or A/C, trips on high pressure in dehumidification mode, and also runs with higher than normal pressures in A/C alone, then the pool heating three-way valve is not shifting completely out of pool heat. (This is assuming that no other cause for a high pressure trip can be found.